Customization: | Available |
---|---|
After-sales Service: | Online Service Support and Free Repair Parts |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
CA Series Air cooled industrial chiller | |||||||||||
Mode Item |
CA-0.6 | CA-1 | CA-2 | CA-3 | CA-4 | CA-5 | CA-6 | CA-8(D) | CA-10(D) | ||
nominal cooling capacity | Kcal/h 50HZ/60HZ |
1290 1548 |
2451 2941 |
4446 5332 |
6803 8163 |
8815 10578 |
11223 13468 |
13115 15738 |
17630 21156 |
22446 26935 |
|
KW 50HZ/60HZ |
1.5 1.8 |
2.85 3.42 |
5.17 6.2 |
7.91 9.5 |
10.25 12.3 |
13.05 15.66 |
15.25 18.3 |
20.5 24.6 |
26.1 31.3 |
||
Total input power | KW | 0.96 | 1.46 | 2.25 | 3.27 | 4.57 | 5.54 | 6.33 | 8.29 | 10.47 | |
Power supply voltage | 1PH~220V 50HZ(60HZ) | 3PH 380V 50HZ(220V/415V/480V 50HZ/60HZ) | |||||||||
(110V 50HZ/60HZ) | |||||||||||
Refrigerant | Type | R22(R134a/R407C) | |||||||||
Control mode | Capillary | Expansion valve | |||||||||
Compressor | Type | Hermetic rotating type | Hermetic scroll type(Piston) | ||||||||
Power(KW) | 0.45 | 0.95 | 1.73 | 2.7 | 3.52 | 4.41 | 5.2 | 3.52× 2 | 4.41× 2 | ||
Condenser | Type | High efficient finned copper tube+ low noise outer rotor fan | |||||||||
Cooling Air volume(m 3 /h) | 750 | 1000 | 2000 | 3000 | 4000 | 5000 | 6000 | 8000 | 10000 | ||
Evaporator | Type | Water tank with coil(Shell and Tube) | |||||||||
Chilled fluid flow(m 3 /h) | 0.258 0.31 |
0.49 0.589 |
0.89 1.068 |
1.36 1.63 |
1.76 2.11 |
2.24 2.68 |
2.63 3.15 |
3.52 4.22 |
4.47 5.37 |
||
Tank volume(L) | 16 | 20 | 25 | 50 | 60 | 70 | 70 | 120 | 200 | ||
inlet/outlet pipe caliber | 1" | 1" | 1" | 1" | 1" | 1" | 1" | 1-1/2" | 1-1/2" | ||
Water pump | Power(kw) | 0.37 | 0.37 | 0.37 | 0.37 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | |
Pump head(m) | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 22 | 20 | ||
Safty protection | Compressor overheating, over current, high and low pressure, over temperature, flow switch, phase sequence, phase-missing, exhaust overheating, anti-freezing. | ||||||||||
Dimension | L(mm) | 530 | 580 | 650 | 930 | 1000 | 1140 | 1140 | 1300 | 1530 | |
W(mm) | 440 | 440 | 500 | 520 | 560 | 560 | 560 | 720 | 780 | ||
H(mm) | 780 | 850 | 950 | 975 | 1070 | 1040 | 1040 | 1310 | 1430 | ||
Weight | Kg | 50 | 73 | 100 | 135 | 150 | 175 | 180 | 310 | 450 | |
Note: 1. nominal cooling capacity calculated according to: Inlet/outlet chilled fluid temperature: 12degree/7degree Inlet/outlet cooling air temperature: 30degree/35degree 2. Working condition: The temperature range of chilled fluid is from 5 to 35degree Temperature difference between inlet and outlet chilled fluid is from 3 to 8degree, It is better to run the chiller while the ambient temperature at or below 35degree. The above red parameters is for the particular voltage, which need to made accordingly. We reserve the right to modify the above information without further notice. For more information about our machines, please contact us now for we support you well |